Abstract

Abstract This paper presents design and dynamic performance investigation of a full‐scale, modular topology (arranged on the sides of a regular hexagon), medium voltage direct current (MVDC) permanent magnet (PM) biased presaturated fault current limiter (PMFCL). This PMFCL represents a cost‐effective design with enhanced longevity, reliability, scalability, and controllability. The scalability of this modular design can be extended by adding or removing CI (letters: CI) core units for different power system applications in a voltage range from to or more. The rated steady‐state (DC) and fault currents of and , respectively. The detection free and self‐triggering performance of this PMFCL is designed and simulated through a 3D coupled model of electric‐circuit magnetic‐field of COMSOL Multiphysics. Accurate representation of PM behaviour, especially in the second quadrant of its hysteresis loop of Jiles‐Atherton method gives realistic performance of the PMFCL. Comprehensive finite element simulations are carried out to study the effect of design parameters on the dynamic performance of PMFCL. Good agreement is found between COMSOL simulation results of DC‐biased PFCL and experimental results of a developed small‐scale prototype. Results reveal that the MVDC PMFCL shows significant improvement and satisfactory performance, in terms of fault current clipping ratio, fault current slope, and power losses, as compared to the conventional MVDC DC‐biased presaturated CI iron‐core fault current limiter (PFCL).

Key findings

  • The PMFCL can limit fault currents up to 10 kA and has a rated steady-state current of 2 kA.
  • The design is modular and can be extended by adding or removing CI core units for different power system applications.
  • The PMFCL has a self-triggering performance and can detect faults without external triggers.